Mounting: Always install the unit vertically to allow for natural heat dissipation.Clearance: Maintain at least 100mm of space above and below the unit, and 50mm on the sides.Temperature: Operate between -10°C and +40°C. If the ambient temperature exceeds 40°C, derate the output current by 3% for every additional degree.Moisture and Dust: Avoid direct sunlight, high humidity (above 95% RH), and corrosive gases. Wiring Diagram and Terminals

OC1 / OC2 / OC3 (Overcurrent): Check for a motor short circuit, heavy mechanical load, or if the acceleration time (P0.11) is too short.OV1 / OV2 / OV3 (Overvoltage): Often occurs during rapid deceleration. Increase deceleration time (P0.12) or install a braking resistor.UV (Undervoltage): Check the input power supply for stability or a loose connection.OL1 / OL2 (Overload): The motor or drive is being pushed beyond its current rating. Check for mechanical jams or reduce the load.OH (Overheat): Ensure the cooling fan is running and that there is sufficient airflow around the heat sink. Safety Precautions invt che100-0r7g-s2 manual

L, N: Connect your single-phase 220V AC power supply here.U, V, W: Connect these to your three-phase motor. (Note: Never connect input power to these terminals).(+) , (-): DC bus terminals for external braking units (if required).PE: Grounding terminal. Ensure a solid connection to prevent electromagnetic interference (EMI). Control Circuit Terminals Mounting: Always install the unit vertically to allow